PRODUCT FEATURES
A family of distributed control products that are open and easy to use, the EXCEL
5000 OPEN System is
a proven performer that defines versatility
Every control device in the EXCEL 5000 OPEN System family uses LonWorks
®
-based open
communications protocol
Third-party LonMark device support allows additional devices from multiple manufacturers to be added
to the existing LON bus
Stand-alone operation at the field control bus level for maximum performance and reliability
Free topology transceiver technology simplifies wiring, uses standard network tools
True integration with fire, security and digital video systems creates application opportunities never
before available
HVAC Controls
Security and Access Control
Americas Version Shown*
Network Router/Firewall-14507780 Series
Specification Data 74-3487
Ethernet and T1 interfaces
AES network encryption capable
Primary Ethernet Network
W7074A/B UL Listed EBI Server
Specification Data 74-3553
Rack mount configuration
Dual Xeon Quad Core Processors
• 16 GB SDRAM (max)
584 GB internal HD storage (max)
Dual 10/100/1000 Gigabit on-board Ethernet
Embedded SCSI & RAID controllers
CD/CDR/DVD and DAT72 tape backup options
EBI Server and Redundancy Option
Microsoft Operating System (see spec & tech document for versions supported)
Remote access server (RAS) supported (see EBI Compatibility Matrix for more information)
Qualified backup solution by Acronis
®
(see EBI Compatibility Matrix for more information)
Server PC Specifications (Standard Performance):
• Dell Pentium 4, 3 GHz, 2 GB RAM, 40 GB HD
Terminal services support for remote access via PDA or other handheld device
• Alarm pager capability for off-site notification including e-mail and SNMP support
Diagnostic tools with remote access capabilities
Quality assurance: ISO 9001, SEI Level 3
Note: This document graphically represents the various systems Honeywell can integrate
and is not to be used for system design.
Go to: www.honeywell.com/ebi for additional information regarding
the powerful EBI software applications.
Go to: www.buildingcontrolworkbench.com for additional information
on the entire offering of Honeywell systems and products.
PRODUCT FEATURES:
The complete solution for the safety and comfort of your people and the effective operation of your buildings
Provides an “enterprise view” that goes beyond traditional building automation, fire and security systems
Fully UL listed to provide authorized operators with two-way command/control of any subsystem from any listed workstation
Allows full interaction between applications to minimize risk to personnel and assets, maximizes personnel productivity and optimizes system and equipment efficiency
Operator segregation allows access only to data and information appropriate for the specific user
Fully scalable from a single application and controller, to enterprise integration with multiple applications and servers distributed across the Ethernet LAN and WAN
Migration platform for a wide range of Honeywell legacy products including Excel Building Supervisor (XBS), Excel Building Supervisor Integrated (XBSi), DeltaNet Excel
Plus, MicroCel, MacroCel, Excel Classic, FS90/FS90 Plus, Delta 1000 and Delta 2000
APPLICATIONS:
Enterprise-wide, integrated sequences of operation allow events in one subsystem to automatically and directly trigger events in another system; Example:
Tenant activates fire alarm pull station
EBI initiates digital video recording and captures the pre-recorded video leading up to the event
Doors are unlocked allowing safe egress while presenting live video to maintain facility security
HVAC initiates proper fan pressurization control for smoke control system operation
Instruction pages and system information is presented to the various operators to manage risk and follow proper emergency procedures
Emergency and routine situations handled with maximum efficiency by bringing the right information together at the correct decision point
Honeywell Enterprise Buildings Integrator (EBI) An integrated facility management solution.
Honeywell EBI is listed for use in the following categories:
UL 864 9th Edition listed
UOJZ Proprietary Protective Signaling System
UOXX Control Unit Accessories
UUKL Smoke Control Systems
UDTZ Signal System Units
• UL 916 – PAZX Energy Management Equipment
UL 1610 – AMCX Central Station Receiving Unit
UL 294 – ALVY Access Control System Units
• UL 1076 – APOU Proprietary Alarm Receiving Units
• UL 2017 – QVAX Process Management Equipment
UL 60951 – NWGQ Information Technology Equipment
• Applicable for use in UL2050, DoD, DCID and SCIF high-security applications
• Listed by ULC for similar applications in Canada
Approved by the California State Fire Marshal, Factory Mutual and additional international agencies
• See individual product specification data sheets for specific approvals
EBI HMIWeb Client Stations
• Static and rotary station licensing
HMIWeb Client browser support
40 simultaneous clients supported
Operator area segregation and permissions enforced
Multi-Monitor support on single client license
Operator definable alarm and event summaries
• Windows 2000, Windows Server 2003 or Windows XP Pro
PRODUCT FEATURES:
Harnessing the power of Honeywell’s patented Distributed System Architecture (DSA), EBI lets you achieve this convenient and seamless
single operator interface without complex engineering, database management or sharing
Reduces training, maintenance and administration costs by employing the same tools for creating graphic displays (for building systems
and process control), configuring points and all system configurations
Supports implementation of occupational health and safety polices
• More effectively leverages your systems investment
APPLICATIONS:
Integrates and controls a plant’s HVAC, lighting, hydraulics and energy usage
Provides primary monitoring and control of plant’s life safety systems with integrated response prompting and tracking capabilities, for
exceptional incident management and regulatory compliance
Integrated access control provides site mustering capabilities to automatically track employees during emergency evacuation situations
Video surveillance and digital video management support permits control room observation of critical processes for informed operational
and safety decisions
Experion Process
Knowledge System (PKS)
Experion Process Knowledge System
(PKS)
Integration – Unlocks benefits via a
unified, collaborative and open architecture that integrates seamlessly to deliver a single
operator environment for plant control, life safety, HVAC, digital video and security.
Honeywell Enterprise Buildings Integrator
TCP/IP LAN, WAN, Internet & Intranet
Open System Integration – EBI supports multiple industry standard communication protocols
to allow enterprise-wide monitoring and control from a single client workstation.
PRODUCT FEATURES:
Client and server support for BACnet, LonWorks, OPC, Modbus and Advanced DDE
Open Interface discovery tools to simplify engineering and configuration of BACnet, LonWorks and OPC Integrations
APPLICATIONS:
Monitoring and control of third-party HVAC central plant and unitary equipment, industrial controls and other systems utilizing Open System
Communication Protocols
• Monitoring third-party Life Safety systems
Integrated system sequences of operation
History collection, trending and global scheduling of third-party open systems
BACnet, ASHRAE STD, SSPC 135
Client/Server Interface, Cimetrics BACstac
BACnet Ethernet & IP Support
• RPM, WPM, COV, Alarm, Schedule, Trend and BBMD
support (See EBI PICs for more information)
EBI BTL Listed, Operator Workstation Profile (B-OWS)
LonWorks
®
Network
ANSI/EIA Std. 709.1
LonWorks Network Services (LNS)
Connectivity via: PCLTA, i.LON
®
600
EXCEL 5000 Open LON and Excel CARE
(see 63-9026 for more information)
Modbus: Gould, Modbus Plus,
Universal Modbus
• Gould Modbus to Modicon 584 and 984 PLCs
RS232 serial interface and Modbus TCP support
OLE for Process Control (OPC)
Read/write of analog and status points
• Item names up to 64 characters
• Multiple LNS databases supported
by single LonWorks Point Server
i.LON
®
600 Router
Provides network connectivity between
Ethernet LAN and LONTalk (FTT-10A) bus
UUKL version available where smoke
control required
LON
LON
PRODUCT FEATURES
CP-600 and 700 family of Niagara
AX
controllers gives onboard IO
and access to a single MSTP bus and/or a single LON bus which
can be used to add additional distributed IO controllers; The
controller is designed for DIN rail mounting and has removable
screw connector terminals
ComfortPoint
Niagara Plant Controller Solution
Honeywell ComfortPoint
®
Native BACnet Solution*
PRODUCT FEATURES
Specification Data SL-53-1092
Supports BACnet Client and Server Operator Work Stations (OWS)
Network connectivity configurations supported include BACnet IP
router, BACnet Controller, Gateway and Web server
• Utilizes BTL listed, BACnet “Native”, Advanced Application
Controllers (AAC)
Each controller functions as a master on BACnet, MS/TP LAN for
peer-to-peer communication
Controllers support the following functionality: Universal inputs and
outputs (varies by model), 10 program objects (fully programmable),
PID loop objects (qty varies by model), 40 analog and 40 binary
value objects, 8 schedule objects, 3 calendar objects, intrinsic
alarm reporting, 8 notification class objects, 8 trend objects (256
samples each), standard applications and fully programmable
control using the ComfortPoint Programming Tool
PRODUCT FEATURES
Specification Data SL-85-3040
Uses Honeywell XL10 family of controllers
Controllers use LonWorks based Open Communications Protocol – when
connected to Niagara-based controller.
Standalone operation at the field control bus level for maximum
performance and reliability
• Free topology transceiver technology simplifies wiring, uses standard
network tools
• ComfortPoint Programming Tool (CPT) contains configuration wizards to
simplify setup and operation of XL10 controllers
LNS Plug-in utilized for configuration when connected via LNS Router
ComfortPoint
LonWorks Solution
BACnet MS/TP Bus
CP-7001 & CP-7051: Advanced
Application Controller for VAV
Terminal Units
Specification Data 85-3013
• UL 916; BTL listed
I/O: 3 universal inputs, 3 universal outputs
• Meets standard VAV terminal unit control
sequences
CP-7001: 18 deg/minute actuator
CP-7051: 60 deg/minute actuator
CP-7003 and CP-7053 Advanced
Application Controller for VAV Fan
Induction Units
Specification Data 85-3014
• UL 916; BTL listed
I/O: 3 universal inputs, 1 universal output, 1
optically isolated triac output, 1 NO
relay contact
• Compatible with CP-1161 and CP-1181 Net
Sensors, and CP-6000 Series Sensors
CP-7003 18 degrees per minute
CP-7053 60 degrees per minute
CP-7301 and CP-7301C Advanced
Application Controller for Air
Handler Units
Specification Data 85-3015
• UL 916; BTL listed
I/O: 4 universal inputs, 3 universal outputs
• Compatible with CP-1161 and CP-1181
net sensors
CP-7301C equipped with real-time clock
CP-7301 without real-time clock
CP-7302 and CP-7302C
Advanced Application Controller
for Rooftop Units
Specification Data 85-3016
• UL 916; BTL listed
I/O: 4 universal inputs, 1 universal output, 1
optically isolated triac output, 2 dual-stage
traic outputs
• Compatible with CP-1161 and CP-1181
net sensors
CP-7401 and CP-7401C
Advanced Application Controller
for Heat Pump Units
Specification Data 85-3017
• UL 916; BTL listed
I/O: 4 universal inputs, 4 optically isolated
triac outputs
• Compatible with CP-1161 and CP-1181
net sensors
CP-7401C equipped with real-time clock
CP-7401 without real-time clock
CP-5801 and CP-5802
Advanced Application Controller
for Direct Digital Control
Specification Data 85-3011
• UL 916; BTL listed
I/O: 8 universal inputs, 8 universal outputs
Supports up to 8 output override cards:
HPO-6701 triac output
HPO-6702 short-protected analog output
HPO-6703 relay, NO contacts
HPO-6704 4-20 mA current loop
HPO-6705 relay, NC contacts
• Compatible with CP-1161 and CP-1181
net sensors
CP-5801 equipped with real-time clock
CP-5802 without real-time clock
CP-FlexStat
Product Manuals: BAC10000 Series
BACnet programmable thermostat,
• Advanced Application Controller (B-AAC profile)
Temperature, humidity and occupancy
sensor versions for packaged system control
applications including: RTU, FCU, HP, and AHU
ComfortPoint Controller Room
Sensor Options NetSensor with
LCD display
CP-1161 & CP-1181 Specification Data 85-3019
Room temperature monitoring and control
9 function keys with 7 user-programmable keys
• Pre-fabricated, quick-connect cables in 25, 50
and 75 foot lengths
CP-1181 includes humidity sensor
CP-6000 Series Sensors
Specification Data 85-3021
Room temperature
Options include: temperature setpoint adjust,
override, override indicator, LCD display and
BACnet MS/TP port
Prefabricated sensor cables in 25, 50 and 75 foot
lengths supported on some models
IO-16-H Optional Onboard
I/O for CP-600
8 Universal Inputs
4 Form A Relay Outputs
4 0-10V DC Analog Outputs
IO-34-H Optional Onboard
I/O for CP-600
16 Universal Inputs
10 Form A Relay Outputs
8 0-10V DC Analog Outputs
• 1 onboard 24V AC/DC Power Supply
Maximum Configuration per CP-600 is
1 x IO-34 and 2 x IO-16’s
CP-600
CP-600
VAV Box Controller W7751
Specification Data 74-2953
Pressure-independent or pressure-dependent VAV
box control
Single-duct/dual-duct VAV box control solutions
Reheat and peripheral radiation control
(selectable "first on" sequencing)
Series/parallel fan
Supply/return air tracking
LonMark functional profile 8010
Constant Volume AHU Controller W7750
Specification Data 74-2956
Proven PID space temperature control algorithm
Integral or packaged economizer control
Separate intelligent recovery rates for heating
and cooling
Demand limit control temperature setpoint in energy
saving direction
LonMark profile 8030
Unit Ventilator Controller W7753A
Specification Data 74-2962
Space or return air temperature control
• ASHRAE cycles 1, 2, 3
8 outputs for HVAC control
PWM or floating damper control
LonMark functional profile 8080
Fan Coil Unit Controller W7752
Specification Data 74-2959
2 pipe, 4 pipe fan coil unit control
Up to 3 speed fan control
With or without electrical reheat
Space freeze protection
LonMark functional profile 8020
Remote Input/Output Device W7761A
Specification Data 74-2698
• Generic I/O for lighting, exhaust fans, pumps and more
LonMark standard objects for sensors and actuators
Communicating Thermostat T7350
Specification Data 63-1299
• For single zone rooftop units, split systems, heat pumps
or hot/chilled water systems
• Two occupied and two unoccupied periods per day
Individual heat and cool setpoints available for occupied
and not occupied periods
P+I+D control minimizes temperature fluctuations
7-day programming
Remote sensor capability for temperature (including
outdoor air and discharge air) and humidity sensors
• Auxiliary contact available for use with economizer or
dehumidification system
Conforms to LonMark Space Comfort Profile for rooftop
applications
Hydronic Controller W7762B/7763C
Specification Data 74-2934
• Radiators, induction units, chilled ceilings and fan coil
units with manual fan switching
High efficiency, low cost heat/cool valve application
solution
• Model with integrated or remote module for wall or
unit mounted
LonMark functional profile 8020
CP-UL6438S – Programmable
Unitary Controller
6 universal inputs
4 digital inputs
3 analog outputs
8 digital outputs
PRODUCT FEATURES
ComfortPoint Programmable LON,
VAV/Unitary Controllers
Specification Data 74-4069-02
Freely programmable with Graphical Function Block Environment
Sylk
Bus – Two-wire, polarity-insensitive power and
communication bus for TR70/TR70-H
Removable terminal strips
Color-coded input/output labels
Internal real-time clock
Internal DC power supply
CP-VL6438NS – Programmable
VAV Controller
6 universal inputs
4 digital inputs
3 analog outputs
8 digital outputs
CP-VL6436AS – Programmable
VAV Controller with Actuator
6 universal inputs
4 digital inputs
3 analog outputs
6 digital outputs
ComfortPoint system shown is representative of supported solutions. Additional products, software options and interfaces may be necessary for a given solution. Contact Honeywell Building Solutions for more information. 1-800-345-6770, ext. 612
LON, LonWorks, LonMark
are registered trademarks
of Echelon Corporation
BACnet is a registered trademark of the American
Society of Heating, Refrigerating and Air Conditioning
Engineers, Inc (ASHRAE)
BTL is a registered
trademark of BACnet
International (BI)
Niagara
AX
is a trademark of
Excel 50 Controller XL50UMMIPC-LON
Specification Data 74-3029
I/O Point Capacity
Analog Inputs: 8 ...........0 to 10 Vdc
....................................0 to 20 mA
....................................(w 499 Ω resistor)
....................................NTC 20k ohm
Analog Outputs: 4 .........0 to 10 Vdc
Digital Inputs: 4 ............3 of 4 fast totalizer
Digital Outputs: 6 .........Triac 800 mA
(all 6 triacs max 2.4A)
Model Type
Excel 50 UPC – without operator interface; Excel 50
UMMIPC-with operator interface
I/O Point Capacity
• 22 physical points
• Up to 256 pseudo points
46 network variables supported on the LonWorks
®
Network
Application module: ......Flash–EPROM
Engineering tool: ..........Excel CARE
Distributed Input/Output Accessories
1 XFR522
Module Type: ...............Manual override for XFL522
Manual Override
Switches: .....................8
2 XFR524
Module Type: ...............Manual override for XFL524
Manual Override
Switches: .....................6
3 XSL511
Module Type: ...............Connector module for
XFL521, XFL522, XFL523,
XFL524
4 XSL512
Module Type: ...............Manual disconnect module
between terminals and I/O
modules
5 XSL513
Module Type: ...............Terminal block for
XFL521/522/523
6 XSL513
Module Type: ...............Terminal block for XFL524
Smart I/O Module
Specification Data 74-3671
XFC3A06001
Terminals: ....................Fixed permanent
Digital Inputs: ...............4
Digital Outputs: ............4
Analog Inputs: ..............4 (20K NTC)
Analog Outputs: ............2 (VDC)
XFC3D06001
Terminals: ....................Removable
Manual Override: ..........6
No. of LEDs: .................10
Digital Inputs: ...............4
Digital Outputs: ............4
Analog Inputs: ..............4 (20K NTC)
Analog Outputs: ............2 (VDC)
C-Bus or LON
UUKL Listed in UL conforming configuration.
C-Bus or LON
Building Network
Adapter (BNA) Q7055A
Specification Data 74-3445
• TCP/IP capable, offers a wide
range of network connectiv-
ity options and online system
diagnostic support
HC900
Specification Data 51-52-03-31
Ethernet (Modbus
TCP) connectivity to EBI
Industrially hardened, hot
swap I/O cards
• Fast updates-27 msec logic,
0.5 sec analog
• High resolution 15 bit universal
analog inputs
Embedded loop auto tuning
C-Bus
Honeywell Building Manager
EXCEL 5000
®
OPEN
System Architecture:
Designed for DDC control versatility and true open system flexibility.
CP-600 and CP-700:
CP-600 Niagara Based Controller
Specification Data 85-3022
• BTL Listed (B-BC Profile)
1 or 2 MSTP port(s) and optional 1 x LonWorks port
IBM PowerPC 440 250 MHz processor
• 128MB DDR RAM & 128 MB Serial Flash
Optional 256 MB DDR RAM
Battery backup
Real-time clock
CP-700 High Performance Controller
Specification Data 74-5093
667MHz 440Epx Power PC
512MB DDR RAM; Upgradable to 1GB
1 GB NAND Flash
Analog Input Modules with
8 Analog Inputs
Panel interface: ............XF821A
LON interface: .............XFL821A
Analog Output Modules
with 8 Analog Outputs
Panel interface: ............XF822A,
XFR822A
LON interface: ..............XFL821A,
XFLR822A
Binary Input Modules with
12 Binary Inputs
Panel interface: ............XF823A
LON interface: ..............XFL823A
Relay Output Modules with
6 Relays
Panel interface: ............XF824A,
XFR824A
LON interface: ..............XFL824A,
XFLR824A
Floating Output Module for
3 Floating Actuators
Panel interface: ............XFR825A
Excel 800 Controller
(XCL8010A)
Specification Data 63-1326
• Panel-Bus supporting 16 Panel I/Os in
any mixture
• Double size application memory
(128KB RACL; Max 192KB application)
30% faster cycle time than Excel 500
Smart with the
same application
381 data-points (software/hardware) in
random IO mix
• DIN rail mounting, fits into fuse boxes
(size 3 DIN43880)
Excel Touch (XI882A)
Color touchscreen interface for
XL50/100/500/800
Home page display with operational
icons
Bus-wide access with login/logout for 3
password levels
Functions supported include: point
monitor and command, trending,
alarming, time programs, fast access
lists and controller information
Product data sheet 63-2682
Zio (TR70 & TR70-H)
Specification Data 63-1322
• Base and "H" model with humidity
sensor
Two-wire, polarity-insensitive, Sylk
bus interface
• Large backlit display with pulldown view
of controller points
Customizable home screens
Sylk
Bus
Network Device Server – 14006700 Series
Specification Data 74-3487
Ethernet to RS232 or RS485 Converter, DB25 connecting via DB25 serial
• 128 – 256 bit AES NIST certified encryption
NexSentry Star II Controller (board only)
P/N 92410250030 Base 2-door Controller
P/N 92410000300 Star Controller Modular Enclosure
P/N 92410450020 4-door Chipset
P/N 92410850020 8-door Chipset
P/N 92411650030 16-door Chipset
Base two-door system can be field upgraded to a 16-door unit
On-board integrated 16 inputs and 4 outputs
Can monitor 255 inputs and control 96 outputs
Modular upgrade options for easy customization and expansion
• Switch selectable baud rate and address for ease of installation
Elevator control up to 96 floors
100,000 cardholder capacity
S-NET dual twisted-pair wire installation for readers and inputs
• 2 on-board Wiegand ports expandable to 16
Ethernet, RS-232, RS-485 and dial-up host communications
Built-in automatic battery charging system
Up to 15 MIRO/WIRO units per controller
OmniProx
OP10
Specification Data 92995100063-B
P/N OP10HON
• Lowest profile HID compatible card reader
Typical read range: 2-3"
Wiegand output
Genuine HID
compatible
OmniSmart OS10
Specification Data 92995100082-A
P/N OS10HON
Contactless smart card reader
OmniProx
OP30
Specification Data 92995100063-B
P/N OP30HON
Mullion size
• Typical read range: 4"
Wiegand output
Genuine HID
compatible
OmniSmart OS30
Specification Data 92995100082-A
P/N OS30HON
Contactless smart card reader
OmniProx
OP40
Specification Data 92995100063-B
P/N OP40HON
Mounts on single-gang electrical box
• Typical read range: 4"
Wiegand output
Genuine HID
compatible
OmniSmart OS40
Specification Data 9299510082-A
P/N OS40HON
Contactless smart card reader
OmniProx
OP45
Specification Data 92995100063-B
P/N OP45HON
• Switch-plate size; Mounts on a UK
size electrical box
• Typical read range: 3 – 4.5"
Wiegand output
Genuine HID
compatible
OmniProx
OP90
Specification Data 92995100063-B
P/N OP90-FWS
• Switch-plate size; Mounts on a US size
electrical box
Vandal-resistant cast zinc-alloy design
• Typical read range: 2"
Wiegand output
Genuine HID
compatible
OmniProx
OP95
P/N OP95-FWS
• Switch-plate size; Mounts on a US size
electrical box
Vandal-resistant cast zinc-alloy design
with piezo keypad
• Typical read range: 2"
Wiegand output
Genuine HID
compatible
SNET
RS-485
Wiegand
TCP/IP Network Adapter
P/N 92410000020
Controller mounted Ethernet LAN module
• 128 – 256 bit AES-certified encryption
SNET
RS-485
Lon
HandKey II
P/N HK-2
Hand geometry reader
Up to 32512 users with
memory upgrade
• Direct enrollment
integration to EBI
Outdoor version available
OmniAssure
Contactless
Smart Card Reader
P/N OT30HON, OT31HON, OT35HON, OT36HON,
OT70HON, OT75HON
Flash-on-card to update reader firmware to
evolving smart card standards
Mullion and switch plate mounting
ADA compliant built-in audible buzzer
• Two LEDs (red and green)
• Configuration cards can be used to manage
security keys and change the operating
characteristics of the reader
Hidden mounting screws deter vandalism
Potted for superior weather resistance
Wiegand output
DR4201
Specification Data 92995100012-D
P/N 92042011000
Low profile DigiReader
HID compatible
• SNET and Wiegand connections
DR4205
Specification Data 92995100043
P/N 92042050100
DigiReader with tamper
DR4208
Specification Data 92995100012-D
P/N 92042081000
HID compatible
• SNET and Wiegand connections
DR4205K
Specification Data 92995100012-D
P/N 92042050000
DigiReader with integrated key-
pad – 24 V
DR4205SCK
Specification Data 92995100013-D
• Universal smart card reader with
integrated keypad
• S-NET and Wiegand connections
DR4203
Specification Data 92995100012-D
P/N 92042030000
Mullion-mount DigiReader
DR4220
Specification Data 92995100012-D
P/N 92042200000
Long-range proximity reader
WIRO 4/8/4 (board only)
Specification Data 92995100050-D
Specification Data 92995100049-D
P/N 92410034840
Additional 8 inputs/4 outputs and
4 Wiegand ports
WIRO 4/8/4 Modular Double
Board Enclosure
P/N 92410000400
MIRO 16/8 Board
P/N 92410020000
Additional 16 inputs/8 outputs and 2 SNET ports
MIRO 32/0 Board in Modular Enclosure
P/N 92410021200
Additional 32 inputs and 2 SNET ports
MIRO 2/24 Board in Modular Enclosure
P/N 92410023200
Additional 2 inputs/24 outputs and 2 SNET ports
TemaServer – Proximity Terminal
P/N TS_TA32, TS_TA33
CPU68EN302 bi-processor including a 68000 (32 bit
architecture) and Onboard Ethernet Controller
• Bi-directional reader with manual swiping for proximity cards
Multi-language management of the user interface
Up to 15,500 cardholder capacity with full time and attendance
functionality
Up to 65,000 transactions stored on a removable cartridge
with Flash EPROM
Lead battery backup, with full functionality for 4 hours in case
of network failure
Tamper protection of the unit to prevent opening
TemaServer – Magnetic Terminal
P/N TS_TA31
CPU68EN302 bi-processor including a 68000 (32 bit
architecture) and Onboard Ethernet Controller
• Bi-directional reader with manual swiping for magnetic
stripe cards
Multi-language management of the user interface
Up to 15,500 cardholder capacity with full time and
attendance functionality
Up to 65,000 transactions stored on a removable cartridge
with Flash EPROM
Lead battery backup, with full functionality for 4 hours in case
of network failure
Tamper protection of the unit to prevent opening
Management of two relay outputs (1A@30V) to command door
unlock and signal external outputs
Tamper protection of the unit to prevent opening
TemaKey – Magnetic Reader
P/N TK_C01
NEURON CHIP
3150 (Echelon) 32 KByte EPROM to download
application firmware
LonWorks
®
(Echelon) connection to the TS_AC01 unit with a
transfer rate of 78 kbps
Alphanumeric graphic liquid crystal display (LCD), backlit, with
two lines of 16 characters
• Bi-directional reader with manual swiping for magnetic cards
(track 2, ISO/ABA 7811 standard)
Numeric-functionkeyboard with 16 keys
One double-colored LED signal: green LED for the correct
reading and red/yellow for invalid
Variable tones for valid/invalid transactions
Management of two dry contact digital inputs to control the
door status
Management of two relay outputs (1A@30V) to command door
unlock and signal external outputs
Tamper protection of the unit to prevent opening
TemaKey – Digital I/O Module
P/N TK_C21
NEURON CHIP
3120 (Echelon)
4 balanced inputs with a range between 0 and 12 V
4 open collector outputs with a range between 0 and 12 V
up to 100mA
TemaServer – Control Unit
P/N TS_AC01/TS2
CPU68EN302 bi-processor including a 68000 (32 bit
architecture) and Onboard Ethernet Controller (TS-2 –
32 bit Freescale Coldfire MCF5471, LINUX OS )
Dialer support with LAN or as a backup to LAN (TS_AC01 only)
Industry-standard LON architecture
Fault tolerant controllers and power supplies
Management of up to 12 doors (16 doors in TS2) with
TemaKeys in both directions
• Management of up to 64 I/O
• 1 MB FLASH EPROM to download application firmware via FTP
(64 MB Flash in TS-2)
• Up to 60,000 cardholder capacity (100,000 in TS-2)
Up to 40,000 transactions buffer (100,000 in TS-2)
Peer-to-peer communication for fast front-end independent
decision making
Onboard clock/calendar chip with automatic management
of DST
Onboard battery backup, with full functionality for 4 hours
(2 hours for TS-2)
Full time and attendance functionality
Web interface for configuration or maintenance (TS-2 only)
LonWorks
®
(Echelon) connection with a transfer rate of 78
kbps
Tamper protection of the unit to prevent opening
TemaKey – Dual Wiegand Interface
P/N TK_S014
NEURON CHIP
3120 (Echelon)
LonWorks
®
(Echelon) connection with a transfer rate of 78
kbps
2 balanced inputs with a range between 0 and 12 V
2 powered open collectors output, holding current 1.2A, peak
max 5A inductive load
Tamper protection of the unit to prevent opening
TemaPower – Power Supply Unit
P/N TP_U01 (0.8A), TP_U03 (4.5A)
LonWorks
®
(Echelon) connection to the TemaServer control
units, with a communication speed of 78 kbps
Protection from power overloads
LED signal: green LED for “correct functioning,” flashing red
for “errors in the communication signal,” red for “device out of
order” and yellow for “Echelon connection is active
Lead battery backup, with full functionality for 4 hours in case
of network failure
Tamper protection of the unit to prevent opening
Control Center 2 (CC2) Keypads
P/N 8003-277
Order # HL-8003277
• Maximum 4 units per system
Status display and local control
• 2 line x 24 character LCD display
Area Keypad (KID)
P/N 8003-220
Order # HL-8003220
• Maximum 8 units per system
• Arm/disarm specific areas
• 6 LED annunciator display
6-Input Concentrator (BIC-6)
P/N 8003-238
Order # HL-8003238
Supervised and tamper protected
6 supervised inputs/outputs
7 segmented LED point alarm/trouble display window
2-Input Concentrator BIC-2
P/N 8003-242; Order # HL-8003242 (White actuator buttons)
2-Input Concentrator BIC-2 HU
P/N 8003-284; Order # HL-8003284
(Red actuator buttons for emergency/panic)
2 supervised inputs
1 output
Supervised and tamper protected
Remote reset
Distress actuator button
Hall Effect Door Switch IV (HEDS IV)
P/N 8003-283
Order # HL-8003283
High-security door contact detector
Supervised and tamper proof
i9000 Remote Intelligent Power Supply (RIPS)
P/N 8003-217
Order # HL-8003217
Maximum 7 units per controller
Powered by 16V AC transformer
Two 400mA, 12V DC switched auxiliary outputs
1A programmable output
Status report to control unit over RS485 comm
RS-232
COMM 1
RS-485
COMM 2
RS-485
I9000 Control Unit
Specification Data 74-3035
P/N 8003-332
Order # HL-8003332
Monitors multiple areas (8 areas maximum)
62 device modular architecture capacity
512 input points with precise identification
64 output points to various equipment and accessories
• 99 user IDs
5 authority levels limiting access to selected functions
Area access – limits access to selected areas
Language preference personalized to each user
• 2 RS-485 communication lines
Power supply included
Wiegand
Ethernet
Intelliguard 9000
Security and Intrusion Detection
PRODUCT FEATURES:
The Intelliguard 9000
(I9000) is a protection system designed to detect intrusions and
other critical conditions when used with the Enterprise Buildings Integrator (EBI).
• The I9000 monitors multiple areas, receiving input and providing localized reporting
and control; A single I9000 control unit can simultaneously monitor many different
buildings, and areas with high-security door sensors
Other compatible detectors and output devices can be added to the system, such as
motion sensors, sound detectors, lights, sirens and buzzers
Multiple regulatory agency listings
• Meets high-security UL Grade A A requirements
• Multi drop EBI configurations (3 I9000's) using RRI and RS-485 bus wiring or
network device server
Temaline A Comprehensive Solution for Security
PRODUCT FEATURES:
Temaline is redefining the concept of integrated security solution subsystems for
today and tomorrow.
Designed for unparalleled system reliability and availability using the “Shared
Load” concept
New distributed architecture and modularity reducing the management load on
the supervisory system
Multi-application/multi-functional controller provides access control, time and
attendance and intruder protection
Optional redundant TemaServer and “Shared Load TemaPower”
Single standalone application to a fully integrated EBI solution
NexSentry Star II Controller Access Control System
PRODUCT FEATURES:
NexSentry
®
Star II controller changes access control standards by offering easy
installation, modular components at an affordable price for the most demanding
access control applications.
Modular architecture allows for easy upgrades to future technologies
Advanced digital technology with embedded Intel
®
32 bit microprocessor
provides the fastest response in the industry
• Support for multiple access technologies including Digital Proximity,
Magnetic Strip, Smart Card, Key Pad and Biometrics
Ethernet
Ethernet
Photo ID Station
Fargo
®
DTC500
• Up to 144 cards per hour
P/N FX-091801
Evolis Pebble 4
• Up to 150 cards per hour
P/N PBL401FRU
USB
Parallel
Parallel
Ethernet
Temaline – Mono Directional Reader
P/N TK_L12, TK_19 HID Compatible
Convenient mullion style
• Reads ISO 14443A/B cards (TK_L12)
• Reads HID proximity cards, 125KHz TK_L19)
Reading distance: up to 4.0cm with HID ISOProx 11TM card (TK_L19)
Host LED control
Anti-removal & tamper contact provide output signal to host
Embedded supervised inputs
Embedded relay outputs (TK_L19)
Embedded open collector outputs TK_L12)
• IP 55 protection
Operating temperature: -20°C/+60°C
TemaKey – Proximity, HID & Smart Card
Reader
P/N TK_C02, TK_C03 HID Compatible, TK_C12 Smart Card
compatible (ISO14443A/B)
NEURON CHIP
3150 (Echelon) 32 KByte EPROM to download
application firmware
LonWorks
®
(Echelon) connection to the TS_AC01 unit with a
transfer rate of 78 kbps
Alphanumeric graphic liquid crystal display (LCD), backlit, with
two lines of 16 characters
Reader for proximity cards, HID with TK_C03 (standard ISO/
ABA 125Khz, up to 5cm reading distance)
Numeric-function keyboard with 16 keys
One double-colored LED signal: green LED for the correct
reading and red/yellow for invalid
Variable tones for valid/invalid transactions
Management of two dry contact digital inputs to control the
door status
Intruder – Galaxy 3 Series Control Panels**
PRODUCT FEATURES:
The Galaxy 3 Series of alarm panels is ideal for commercial and industrial
applications. The range comprises of three control panels, the Galaxy 3-48, the
Galaxy 3-144 and the Galaxy 3-520, which allow expansion up to 48, 144 and
520 zones respectively. The new panels are fully compatible with Galaxy 8,
18, 60, 128, 500, 504 and 512 alarm systems, allowing an easy upgrade from
existing Galaxy installations to the new 3 Series. Galaxy 3 Series panels also
have the easy-to-use Galaxy programming interface. Features in the 3 Series
panel range include:
16 on-board programmable zones with 8 on-board programmable outputs
• Improved communications performance via an on-board RS232 port and an
optional integrated PSTN dialer/modem
Integrated, intelligent power supply that provides diagnostic information
suitable for the requirements of PD6662/prEN50131-1:2004 Security Grade
3 installations
581 6H Universal Contact
Door and window protection
Two loop transmitter
Built-in magnetic reed switch
• Allows wired detector to signal to wireless receiver
DT-725D/P DUAL TEC
®
Motion Sensor
with K-Band Technology
Ability to adjust the microwave down to suit the
characteristics of a 3m room
• K-Band technology, 35mA @ 12V dc
Operating temperature: -10°C to +55°C
• EN50131-1 Security Grade 2, Environmental Class II
**North America approvals pending
Galaxy 3-48 Control Panel and
Galaxy Dimension GD-48, GD-96,
GD-264, GD-520
GD-(XXX) represents total zones supported
• Integral 1.5A (0.5A @ Grade 3) power supply
and communicator
• 16 zones expandable up to 48 zones
8 outputs expandable up to 24 outputs
• Support for 8 remote keypads (or 3 Keyproxs)
• 500+500 event log
100 Users
• 4 Groups
• 64 Links
Galaxy peripherals support
PC applications for remote servicing
Mk7 Keypad
Stylish design
Tactile, backlit rubber buttons
Set/unset system with PIN number
Provides full system control tamper protection
• Connected directly to the Galaxy panel
(via direct cable connection) but can be mounted up to
1000m from the control panel
32 alpha-numeric character, back-lit display
Auto summertime change
5802H Panic Alarm
Sleek design, fully supervised portable panic alarm
Dual button action
• Use as a pendant or belt clip
User-replaceable lithium battery
LED transmission indication
P026-0-B
Galaxy Power RIO
• Boxed 2.75A PD6662:2004 (prEN50131-1:2004)
Security Grade 3 intelligent power supply
Reports AC, battery and fuse status to the Galaxy
control panels as well as tamper information over
the Galaxy RS485 interface
• A Galaxy RIO is integrated in the unit providing 8
programmable inputs and 4 outputs
DT7360UK Dual Technology
Motion Sensor
• Ceiling mount, 360 degree field of view mirror
technology PIR, Dual Tech K-Band sensor
• EN50131-1 Security Grade 2, Environmental Class II
• Dimensions: 130mm x 130mm x 60mm (H x W x D)
• Range: 360° – 15m diameter
DT900/ Dual Technology Detector
• Range: 27m x 21m – 15m x 12m (Selectable to 15m x 12m)
Vandal resistant housing, bug guard
INFORMER
Circuit identifies range reduction
Microprocessor controlled, concurrent diagnostics, separate
Alarm, Anti-Mask and Trouble relays
X-Band technology, 10,687Ghz Frequency
Operating temperature: -10°C to +49°C
• Power requirements: 10~15V dc, 50mA @ 12V dc
Tamper switch
• Dimensions: 134mm x 178mm x 210mm (H x W x D)
• EN50131-1 Security Grade 3, Environmental Class II
FG701 Glassbreak Simulator/Tester
Compatible with all IntelliSense and ADEMCO glassbreak
detectors, all manufacturers
Remote test mode activation operates from approximately
5 meters away when used with FG1600 Series
Glassbreak Detectors
Calibrated signal output to allow true range verification
Low battery announcement
Digitally produced glassbreak sound
FG625TAS
FlexGuard
®
Glassbreak Detector
• Selectable sensitivity, mount anywhere, surface mount
design, all glass types
• Power requirements: 6~18V dc,12mA @ 12V dc
Tamper switch
Compatible with the FG701 breakglass simulator
• Dimensions: 98mm x 6mm 2x21.8mm (H x W x D)
• Range: 7.6m – 360° (adjustable range up to 7.6m)
• EN50131-1 Security Grade 3, Environmental Class II
PRODUCT FEATURES
The VISTA-128BPE/VISTA-250BPE is an eight partition, 128/250 zone UL commercial
burglary control panel that meets the demanding requirements of today’s commercial
installations while simplifying end-user operation. A revolutionary new feature called
Panel Linking allows multiple partitions, panels – even buildings – to be armed,
disarmed and have status checked all from one location. Up to eight VISTA-128BPE/
VISTA-250BPE panels can be linked together.
Honeywell Security Manager
VISTA-128BPE/VISTA-250BPE
Partitioned Commercial Burglary Alarm Control Panel
• Provides nine style-B hardwired zones, up to 119/241 additional zones
using a built-in polling (multiplex) loop interface with EOLR supervision sup-
porting N.O. or N.C. sensors (optional for zones 2-8)
• Supports up to 128/250 wireless zones using 5881 type RF receiver
Provides the ability to control eight separate partitions independently
Accommodates 150/250 user codes with seven authority levels
Accommodates 32 keypad macro commands per system
• Scheduling capabilities including open/close schedules, holidays, timed
events, access schedules and end user outpour programming
• Supports up to 16 two-wire smoke detectors on zone 1
• Supports up to 50 latching-type glassbreak detectors on zone 8
• Supports up to 96 programmable relays
XLS-NET
Twisted Copper Pair
XLS-NET
Fiber Optic Cable
XLS-NET Telephone Lines
Fire and Life Safety Systems CCTV & Digital Video
Asset Tracking Energy Applications
Wide Area Network/Internet (WAN)
Local Area Network (LAN)
Enterprise Systems Integration
Share information with personnel, office and financial system databases.
PRODUCT FEATURES:
• Flexible cardholder database import/export capabilities offering interfacing options to ERP systems such as PeopleSoft,
SAP, etc. for periodic or on-demand database synchronization
Microsoft SQL Reporting Services and Open Database Connectivity (ODBC) support allows read-only access to EBI point,
history and event data for enhanced EBI or third-party system analysis and reporting
APPLICATIONS:
Changes made to personnel information in the HR database are automatically sent to the EBI CMS to update area and
equipment access information
Events in the EBI CMS sends information to the HR system for time and attendance or after-hours billing reporting for
energy and services
Honeywell Instant Alert
®
Plus utilizes Web-based emergency communications for immediate worldwide notifications via
phone, cell phone, e-mail, pager, text message, PDA and fax. Supports real-time reporting and two-way interaction for
automated teleconferencing and feedback. Specification Data Sheet SL-53-2065
Global HRMS &
PeopleTools support
Interface to SAP R/3 Human
Resources Module
ODBC
Network
Firewall
Distributed System Architecture (DSA)
Provides centralized monitoring for geographically distributed systems, and scalability for large enterprise systems.
PRODUCT FEATURES:
Integrates multiple servers, each performing a different application: HVAC, Security, Life Safety, Industrial Control
DSA for points and DSA for cardholders allows Operator Client Stations consistent access to both local and remote points and cardholder data
Extends the capacity of a single server solution to support additional points, channels and controllers
• Utilizes Windows 2000 Server or Windows Server 2003
APPLICATIONS:
• The HVAC system and security system operate independently and share data to optimize occupancy scheduling, lighting and energy management
strategies based on information from both systems
Cardholder data may be managed from a single client on a single server in a “Traveling Card” concept allowing cardholders to move between sites
EBI DSA Server
EBI DSA Server
Corporate Intranet, VPN or WAN
Intranet and Internet Access
Connectivity options allow access from anywhere in the world via HMIWeb Client and
Browser Stations, or Web page access via Web Toolkit and Web Point Control optional interfaces.
PRODUCT FEATURES:
HMIWeb browser station utilizing Microsoft Internet Explorer (IE) provides full client access with
operator permissions and area segregation enforced
EBI systems with TCP/IP network access and the network server option may also utilize Web Toolkit
pages with Active X controls for analog and status point monitoring and control
Web Point Control utilizes Java Applets to allow status point control and allow users to define schedules
up to one week in advance
APPLICATIONS:
Users away from the office may access their EBI system using VPN, or through a thin client access over
the internet to check system status, issue commands, respond to alarms, or request reports
ServiceNet, Honeywell Remote Monitoring provided by the Honeywell Global Service Response Center
(GSRC) via intranet, VPN or internet connectivity (ref SL-56-7745)
Honeywell Software Update Service (SUS) for EBI is both a management console and a service; SUS
provides installation and management of the latest qualified Microsoft and EBI software updates as well
as system policies to ensure optimal system performance and improved security; SUS is available on a
subscription basis (ref SL-53-1091 & SL-53-1089)
HMIWeb Client Browser Station
Internet Explorer Web Toolkit
EBI Web Point Control
Network
Firewall
Network
Firewall
SOAP API interface for
emergency global notification
Instant Alert
®
Plus
Honeywell Asset Locator
A real-time active Radio Frequency Identification (RFID) location tracking
and monitoring solution for protecting the vulnerable in healthcare and
museum environments.
APPLICATIONS:
Infant abduction deterrence
High-risk patient supervision
Real-time lost patient tracking
Unauthorized baby handling
Exit/entrance security supervision
Hands-free access control
Patient movement and auditing
24/7 wireless duress alarming
Asset location tracking and theft deterrence
Staff safety (location tracking and duress alarming)
Honeywell Asset Locator
Ethernet
LON
i.LON 600 LonWorks /IP Server
Provides network connectivity between Ethernet LAN and the LONTalk (FTT-10A) bus
• Handles up to 256 devices
• UL Listed & CE compliant
Controls up to 9 physical layer repeaters
Physical Layer Repeater
Extends the IR/IR location reader network beyond 64 nodes and extends the length of
the free topology BUS by 1640 feet/500 meters
• Handles up to 50 IR or RF location readers
Up to 9 PLRs per LON channel (per iLON 1000
®
router)
Elpas IR Location Reader
A fixed receiving device, easily ceiling or wall-mounted, that detects, processes and
transmits over the LonTalk network the coded 433MHz infrared (IR) messages emitted
by Elpas active RFID tags and badges
• Provides accurate room-specific location data
• Factory programmed unique ID code
• Adjustable circular coverage area, up to 40 feet/12.2 meters
On-board audiovisual status indicators
Architecturally attractive and unobtrusive
• FCC & CE compliant
Elpas NXB External Relay Box
An output interface for controlling external devices such as door locks, security lights
and alarm annunciators
• FCC & CE compliant
Multiple Status LED indicators
• Local connection to IR/RF location readers
Two normally open or normally closed relays
• Each relay handles up to 250V at 5.0 amps
Elpas RF Location Reader
A fixed receiving device, easily ceiling or wall-mounted that detects, processes and
transmits over the LonTalk network the coded radio frequency (RF) transmission
messages emitted by Elpas active RFID tags and badges
Provides general area location data
• Factory programmed unique ID code
• Adjustable circular coverage area up to 40 feet/12.2 meters
On-board audiovisual status indicators
Architecturally attractive and unobtrusive
• FCC & CE compliant
Elpas Low Frequency Exciter
A fixed, low power wireless emitter, easily ceiling or wall mounted, that adds
instantaneous exit/entrance security intervention alarming to any RFID installation
Pinpoint detection functionality for doorways and open entrance/exit areas
• Factory programmed unique ID code
• Generates an adjustable sphere shaped magnetic (125 KHz) field up to 10 feet
/3.0 meters
Master/Slave configurations for double doors or larger open areas
Architecturally attractive and unobtrusive
• FCC & CE compliant
Elpas EJB Junction Box
A low voltage type junction box for interconnecting the RF/IR location readers, the LF
Exciters, the LON data BUS and the 24V/DC power supply
Power status LED indicator
Small, lightweight, unobtrusive
• FCC & CE compliant
Elpas Infant Protection Bracelet
Comprised of a rechargeable tag attached to a disposable non-latex tamper anklet
band the bracelet provides 24/7 automatic infant abduction identification and safety
protection
Automatic tampering and removal warnings
Supports exit/entrance security intervention alarming
Adjustable, latex-free disposable anklet bands
Triple technology RF/IR/LF signaling technologies
Ultra-small, easy to clean tag design
Tough, shock proof, IP66 water-rated tag housing
Internal rechargeable Lithium ion battery pack
• CE and FCC compliant
Elpas Healthcare Positioning Tag
Intended for the real-time monitoring and tracking of patients or medical personnel,
wireless duress signaling and hands-free access control
Supports exit/entrance security intervention alarming
Single-button, wireless nurse call/personnel duress alert signaling
Triple technology RF/IR/LF signaling technologies
Watchband, disposable wrist band, pendant lanyard options
• Small tag size and weight
Tough, shock proof, IP66 environmental housing
Compact Lithium long-life replaceable battery
• CE and FCC compliant
Elpas High Risk Patient Bracelet
Comprised of a rechargeable tag attached to a disposable non-latex tamper wrist band,
the bracelet delivers automatic 24/7 real-time location tracking of patients that exhibit a
high-probability of Wandering or Elopement
Automatic tampering and removal warnings
Supports exit/entrance security intervention alarming
Adjustable, latex-free disposable wrist bands
Triple technology RF/IR/LF signaling technologies
Ultra-small, easy to clean tag design
Tough, shock proof, IP66 water-rated tag housing
Internal rechargeable Lithium ion battery pack
• CE and FCC compliant
Elpas Personnel Badge
Engineered to look like industry-standard photo ID personnel badges, the device
provides real-time monitoring and location tracking of personnel or visitors, wireless
duress signaling and hands-free access control
Supports exit/entrance security intervention alarming
Single-button nurse call/personnel duress alert signaling
Triple technology RF/IR/LF signaling technologies
Tough, shock-proof, water resistant housing
Compact Lithium long-life replaceable battery
• CE and FCC compliant
Elpas Asset Tracking Tag
Used for the real-time monitoring and tracking of portable assets or individuals;
Wireless duress signaling and hands-free access control
Automatic asset tampering and removal warnings
Supports exit/entrance security intervention alarming
Optional wireless emergency or duress signaling
Triple technology RF/IR/LF signaling technologies
• Asset, belt clip or pendant mounting options
Ultra-small tag size and weight
Tough, shock proof, IP64 environmental rated housing
Compact Lithium long-life replaceable battery
• CE and FCC compliant
Twisted PairFiber Optic Cable
DeltaNet FS90
Capability, Reliability, Expandability
PRODUCT FEATURES:
The DeltaNet FS90 Fire and Security (F&S) family of real-time, microprocessor-based
controllers offers conventional and intelligent fire detection and annunciation, security and
access control.
Building on the base FS90 system architecture, the family includes:
• DeltaNet FS90 System for conventional zone alarm verification, cross-zoning,
annunciation, control, individual zone alarm, supervisory and trouble indication, zone
disconnect switches and a local audible signal; Security functions include local and
remote secure/access switching and high-security line supervision
• DeltaNet FS90 Plus System (“FS90 Plus”) for intelligent functions to monitor and
control individually addressable fire and security devices. FS90 Plus can have up to nine
Intelligent Loop Interface Boards, each of which can have two 2-wire circuits or one
fault-tolerant 4-wire circuit
DeltaNet Access Control for monitoring and control of up to eight card readers and/or
keypads per controller. The system supports multiple card technologies, multilevel anti-
passback, two-card access, supervisor-required access and elevator control
DeltaNet FS90 Fire and Security Controller
Specification Data 74-3154
Conventional and intelligent detection and signaling
Standalone operation and/or integration with higher order systems
Function boards for configuration to site requirements
• Easily changeable data file in nonvolatile memory
Auto-tuning sensitivity
• Communication to panels via dual twisted pair, leased telephone lines or fiber
optic cables
DeltaNet FS90 Fire Command Center
Specification Data 74-3154
Any DeltaNet F&S system, whether standalone or connected to a higher-order system, can
include an optional command center for alarm and trouble message display and optional
printout, and for data display and entry from a keypad
XLS1000 F&S Bus Interface – 14507532
Specification Data 74-2771
Fully compatible with the DeltaNet F&S bus architecture, this interface allows XLS1000
controllers to coexist with the FS90 on the F&S bus, providing a seamless migration path for
customers
DeltaNet FS90 Access Management Controller (AMC)
Specification Data 74-2438
FS90 functions or operate as a dedicated access system
Fully integrated with EBI
Support for major access card technologies, including magstripe, barrium ferrite,
proximity, Wiegand and biometric readers
Complex access control applications such as elevators control, multi-level anti-passback,
two-card, supervisor rules, PIN support and over 200 schedules per controller
FS90 Control and Communication Function Boards
Part Number Board Function
14505104-005 CA FS90 control/CPU board
14506344-001 LJ RS485 communications and display board
14506690-001 LJ Leased line communications and display board
14506302-002 SB/SD Two position manual switch – 4 circuits
14506302-001 SH/SK Three position manual switch – 4 circuits
Fire/Security Function Boards
Part Number Board Function
14506106-001 AA Class “B” initiating device circuit – 4 zones
14505108-001 AB Class “A” initiating device circuit – 2 zones
14505106-002 AC Class “B” initiating device circuit – 4 zones – contact input only
14505118-001 AD Digital input – 8 circuits, unsupervised
14505132-002 AE Intelligent detection loop (slc) – 2 circuits per board
14505188-001 AF Class “B” secure/access circuit – 4 zones, with local control
14505188-002 AG Class “B” secure/access circuit – 4 zones, no local control
14506432-001 AH Class “B” ul grade aa high-security circuits
14505110-001 BF Class “B” notification appliance circuit – 2 NAC circuits, 2 N.O. Relays
14505110-002 BG Class “A” notification appliance circuit – 2 NAC circuits
14505116-001 DB Digital output – 8 circuits
14505112-001 DC Accessory relay board – 4 SPST N.O. OR N.C. relays
FS90 LAN Interface Assy – 14006700-598100
Specification Data 74-3487
Specification Data 74-3646
Configurable for single or dual Ethernet networks
Converts Ethernet to RS232/RS485 with optical isolation for UL Fire/Security applications
Supports 128-bit AES encryption
PRODUCT FEATURES:
As a standalone system, or as a network of distributed panels, Honeywell’s intelligent
fire alarm control panels meet virtually every application requirement from small to large
integrated systems. Designed with a high degree of modularity and for ease of
system planning, these panels can be configured with just a few devices for small building
applications or for integrated campus and commercial installations. Intelligent sensors deliver
unique customer value such as:
Eclipse
– a true peer-to-peer communication protocol and distributed intelligence that
allows field devices to respond to an alarm condition in less than 1⁄2 second
SMART – a patented maintenance tracking and reporting solution that ensures your fire
alarm system is been tested properly
High-speed/patented smoke detection technology:
FlashScan
®
Intelligent features
Poll 318 devices on each loop in less than one second
Activate up to 159 outputs in less than three seconds
• Fully digital, high-precision protocol (U.S. Patent 5,539,389)
Advanced Warning Addressable Combustion Sensing (AWACS™) – nine levels
Multi-detector algorithm involves nearby detectors in alarm decision
(U.S. Patent 5,627,515)
Automatic detector sensitivity testing
Voice Communication
Integration of multiple building Mass Notification Systems over traditional copper or
fiber medium, including TCP/IP enabled XLS Networks
Excel Life Safety System – XLS120
Specification Data 85-3001
• Complete, self contained fire alarm panel for small buildings or network installation
One isolated intelligent Signaling Line Circuit (SLC) Style 4, 6 or 7
• Up to 159 detectors (any mix) and 159 modules per SLC
Standard 80-character display, or display-less (a node on a network)
• Network option – up to 103 nodes supported of any node type using wire or
fiber-optic connections
Selectable system sensor strobe synchronization
Excel Life Safety System – XLS140-2
Specification Data 85-3128
One, expandable to two, isolated intelligent Signaling Line Circuit (SLC) Style 4, 6, or 7
• Up to 159 detectors (any mix) and 159 modules per SLC
Standard 80-character display, 640-character large display, or display-less
(a node on a network)
Network option – 103 nodes supported (XLS140, XLS-NCA Network Annunciator) using
wire or fiber-optic connections
Selectable system sensor strobe synchronization
Excel Life Safety System – XLS-NCA2
Specification Data 74-4045
640 character – enhanced LCD display
Printer, CRT and keyboard interfaces
User interface for all points in all nodes on the system
Can be used as a separate annunciator or combined in the XLS140 cabinet
Supports additional 32 remote ACS annunciator modules
XLS3000 with Digital Voice Command
Specification Data 74-4034
One to ten isolated intelligent Signaling Line Circuits (SLC), Style 4, 6, or 7
• Up to 159 detectors and 159 modules per SLC, 318 devices per loop/3,180 per
FACP or network node
Large 16 line, 640 character LCD backlit display or use display-less as a network node
Network option supports the XLS3000, XLS140, XLS-NCA2 Network Annunciator,
XLS-DVC-EM and Honeywell Enterprise Buildings Integrator (EBI)
Support CLIP, FlashScan and Eclipse detector protocols
• 4,000 event history file in nonvolatile memory, plus a separate 1,000-event alarm-
only file
Autoprogramming, walk test, positive alarm sequence and time scheduling
Honeywell SMART maintenance reporting
Excel Life Safety System – XLS-FRI
Specification Data 85-3134
Large intuitive display shows building floor plans with respective active fire alarm
devices, water supplies, evacuation routes, access routes, gas, power and HVAC
shutoffs, and chemical and structural hazards in the building
Detailed information for active devices or critical building icons on the floor plan
• Easy access to building, emergency contacts, site plan and alarm event information
Excel Life Safety System – XLS140/XLS3000/XLS-DVC
Advanced Detection, Networking and Voice Communication
Honeywell Life Safety Manager
Modules, Amplifiers, Power Supplies and Boards
Part Number Function
3-LDSM LED display support module
3-24R (Y/G) 24 red LED display module (yel/grn)
3-12SR (Y/G) 12 switches/12 red led display/control modules (yel/grn)
3-12RY 12 red LED and 12 yellow LED display modules
3-12/S2Y 12 switches, each with 2 yellow LED display/control modules
3-12/S1GY 12 switches with one green and one yellow LED per switch
3-12/S1RY 12 switches with one red and one yellow LED per switch
3-6/3S1G2Y 6 groups of 3 switches; Each switch has (1) green, (2) yellow LEDs
3-6/3S1GYR Control/display module with six groups of three switches; Each switch has
one green, yellow, red LED
3-ZA20A/B 20W zoned amplifier; Selectable for 70 or 25 Vrms operation
3-ZA40A/B 40W zoned amplifier; Selectable for 70 or 25 Vrms operation
3-ZA90 90W zoned amplifier; Selectable for 70 or 25 Vrms operation
3-PPS/M Primary power supply with local rail module 120v, 50/60 hz
3-IDC8/4 Initiating device circuit module
3-OPS Off premises signaling module
3-ASUFT Audio source unit with local microphone and firefighter’s telephone
3-CPU1 Main panel processor
3-LCD Main display interface with LCD
3-RS485A/B/R Network communication board
3-RS232 RS232 communication board
3-FIB/A Fiber optic communications interface
3-MODCOM(P) Modem communicator DACT with duplex V.32 bis 14.4K baud modem
3-NSHM1/2 Network short haul modem communications interface with modem
connections
3-SAC Security control module
XLS-KPDISP Keypad/display module
XLS1000 Primary System Components
Part Number Function
3-DSDC Dual SIGA data controller with one SIGA data board; Mounts to local rail
3-AADC Analog addressable data loop controller; Mounts to local rail
Excel Life Safety System (XLS) – LAN Interface
32004871 Series
Specification Data 74-3444
One XLS LAN Interface serves entire XLS200/1000 subsystem:
- XLS system point display and command from any EBI workstation
- Up to 40,000 points available from 64 XLS nodes
- XLS points served via XLS high-speed peer network
• Meets requirements of UL864 UOJZ for fire alarm control unit and UL1076 for
security applications
24 Vdc power supplied directly from XLS1000
RS485 Audio & Data Twisted Copper Pair
Short Haul Modems
24 ga Telephone Lines
Audio & Data Fiber Optic Cable
Flexible Network
Communication
Topology
PRODUCT FEATURES:
Honeywell LifeSafety Manager provides unprecedented protection of your building’s assets
and occupants. This life-safety application incorporates:
Intelligent, microprocessor-based devices, including multi-sensor detectors that provide
early warning of smoke and fire conditions, and virtual elimination of nuisance alarms
Advanced distributed, digital audio communication system facilitating safe, orderly
evacuation of occupants
Rapid and reliable fire alarm controller peer-to-peer communications network
Integral firefighters telephone communication system
Emergency paging to support storm warning and hazardous materials
(HazMat) notification
Control of the facilities’ HVAC equipment, such as fans and dampers, to contain smoke
and create safe havens
• Releasing of fire doors to permit safe exit
Sprinkler supervisory status of suppression systems, sprinkler valves and fire pumps
Excel Life Safety System – XLS1000
Specification Data 74-2073
• Modular system designed for medium to large building and campus applications
168-character LCD automatically displays system messages and alarms
64 node, 160,000 points with 3-second alarm response over any size network
Total network wiring over 300,000 ft (91,440m)
250 devices per loop, 2500 devices per node
750 ms signature loop alarm response
Every point can be viewed and controlled from any node
• Digital storage and transmission of eight multiplexed channels of audio for
unmatched intelligibility
Local, proprietary and central station operations with integral alarm printer option
Modem communicator option with DACT functionality
• Graphic, text/LED and keypad/display annunciator options
Listed for suppression releasing and smoke control applications
Excel Life Safety System – Envoy Annunciator
Specification Data 74-3481
High-contrast lines and text
LCD displays custom text messages in graphic annunciator enclosure
- Firefighters smoke control station options
- Agency listed with Honeywell control panels
- Surface or semi-flush mounting with optional trim
- Field-installed modification of graphic with optional graphic transfer kit
Excel Life Safety System – Remote Annunciator
Specification Data 74-2888
Backlit LCD display provides 168 characters
- Displays information important to user
- Hands-free, first and last event with highest priority
LCD display uses queues to sort events
Variety of cabinet configurations size the annunciator to the application
• Programmable LED flash rates
Slide-in custom labels
Excel Life Safety System – Flexible Network Communications
Supports communication on:
- Twisted pair copper
- Single and multi-mode fiber optic cable
- Existing dry telephone lines
Excel Life Safety System – XLS1000
A High-Performance Life-Safety Solution
Excel Life Safety System (XLS) – Fire Network Adapter
(FNA3)– Q7055C series
Specification Data 74-4080
TCP/IP offers wide range of network connectivity options
Online system diagnostic support
Using the XLS-NCM interface, up to 100 nodes can be connected to the EBI through a single interface
With optional EBI software, provide VoIP integration for mass notification systems
• UL864 (UOJZ) 9
th
Edition listed for full control of the system
Excel Life Safety Sensors
Model Type Features
Compatibility
FS90 XLS1000 XLS120 /XLS140 XLS3000
Eclipse Series
TC906
TC907
TC908
Photoelectric
Ionization
Thermal
Built-in fault isolation and distributed intelligence for true Style 7 SLC operation
Peer-to-peer digital communication between devices minimizes interference and provides extremely fast
response times to alarms
Smoke sensors include Aclimate
self adjusting algorithm to maintain optimum sensitivity while minimizing
false alarms
Heat sensors are configurable for fixed temperature setpoint: 135°F (57°C), Rate-of-rise detection: 15°F/minute
(8.3°C/minute); High temperature heat: 190°F (88°C)
LED operation is configurable based on operating mode
Supports Honeywell SMART maintenance reporting per device
Yes
Smoke
TC806
TC807
Photoelectric
Ionization
Low-profile design, low current draw
Tamper-resistant wiring base
Integral insect resistant screen to reduce nuisance alarms
Dual LEDs provide 360-degree viewing
Optional remote LED annunciator
Built-in test mechanism
Yes Yes Yes Yes
XLS-IS
XLS-PS
Photoelectric
Ionization
Environmental compensation
Pre-alarm sensitivity capability
Continuous self-diagnosis and storage of environmental and operational data
Day/night sensitivity adjustment
One red and one green status LED
Standard, relay and fault isolator mounting bases
Design and manufacture per ISO 9001 standards
Yes
Yes
Heat
TC808 Thermal
135° ROR/FT
190° FT
Thermistor sensing circuit for fast response
Rate-of-rise detection model available
Dual sensor LEDs provide 360-degree viewing
Modern low-profile design
Compatible with Honeywell CLIP and FlashScan loop transmission
Yes Yes Yes
XLS-HFS
XLS-HRS
Fixed Temperature
135° FT
Rate of Rise
135°F (57°C) fixed temperature detector type
Combination 15°F (9°C) per minute minimum rate-of-rise and/or 135°F (57°C) fixed temperature detector type
Electronic addressing and device mapping
Continuous self-diagnosis and storage of environmental and operational data
Standard, relay and fault isolator mounting bases
Yes
Yes
Special Applications
TC840
Acclimate
Multi-Criteria
Photoelectric
Thermal
Automatically optimizes performance for each installed location
Continuous monitoring of detector sensitivity
Digital pulse-width encoded communication with noise immunity
Compatible with Honeywell CLIP and FlashScan
intelligence
Yes Yes Yes Yes
FAAST
Fire Alarm Aspiration Sensing Technology Detection as precise as 0.00046 %/ft obscuration
Five alarm levels and two sensitivity modes provide application flexibility
Dual flow detection including both ultrasonic and electronic sensing for pipe and chamber air flow measurement
A single device protects up to 8,000 square feet
Advanced detection algorithms reject common nuisance conditions
Patented particle separator and field-replaceable filter remove contaminants from the system
PipeIQ
software provides intuitive system layout, configuration and monitoring all in one package
Onboard Ethernet interface enables remote monitoring and e-mail status updates
Fault indictors exhibit a broad spectrum of events
Unique air flow pendulum graph verifies pipe network functionality
Particulate graph displays subtle environmental changes for early problem indications
Yes Yes Yes Yes
TC846
Pinnacle
Ultra-High Sensitivity Laser Smoke
Detector
0.02%-2.00%/ft
Obscuration
Fast response to detect very early particles of combustion
Ultra-high sensitivity capability
On-board drift compensation
Transient rejection algorithms
Environmental tracking
Wide sensitivity range
Yes Yes Yes Yes
TC847A Single-Ended Beam Smoke Detector 16 to 328 ft protection range
Single-ended, reflective design
User friendly alignment procedure
Six user selectable sensitivity levels
Integral NFPA 72 sensitivity test feature
Removable plug-in terminal blocks
Digital display for easy alignment
Built-in automatic gain control compensates for signal deterioration from dust build-up
Paintable trim ring with enamel or acrylic-type paints
Yes Yes Yes Yes
XLS-IPHS MultiCriteria
Ion, Photo, Heat
Environmental compensation
Wide 0.67 percent to 3.70 percent/ft sensitivity range
Pre-alarm sensitivity capability
High ambient temperature operation (up to 100°F [38°C])
Yes
XLS140/XLS3000 Primary System Components
Cabinets, Chassis and Power Supplies
CHG-120 Battery charger, 25-120 Ah gel cell; Mounts on Chs chassis or in Xls-Lbb box
CHS-2D Mounting chassis for Xls-Nca2 used in Xls-Abs-2D cabinet mounting chassis for Xls-Nca2 used
in Xls-Abs-2D cabinet
CHS-4MB Second row chassis assembly; Includes Mp-1B, Chs-4N (“N” is the Chs-4 with different depth)
and expander ribbon cable
CHS-4N Chassis, mounts Lcm-320/Lem-320, Xls-Lcm-320/Lem-320, Ncm-W/F; Mounts in rows 2-4
CHS-M2 Chassis assembly – 1st row; Order one for each Xls-140
HPF24S6 24VDC UL Listed Fire Alarm Nac Expander, 6A synchronized
HPF24S8 24VDC UL Listed Fire Alarm Nac Expander, 8A synchronized
HPF602ULADA 24VDC UL Listed Fire Alarm Nac Expander, 6A
HPF902ULADA 24VDC UL Listed Fire Alarm Nac Expander, 9A
SBB-x4 Primary system enclosure, red or black, 4 sizes available
XLS-ADDR-x4x Primary system enclosure door, red or black, matches SBB-x4, DVC applications
XLS-DR-x4Bx Primary system enclosure door, red or black, matches SBB-x4
XLS-ABS-2D Annunciator back box, surface (or semi-flush)
Annunciator Modules and Controls
ACM-xxx ACS annunciator; Up to 96 points of annunciation with alarm LED, trouble LED and switch
per circuit
ACM-8R Remote form-C relay module; 8 form-C relays driven by EIA-485
LCD-80TM 80 character terminal mode only LCD annunciator
LDM-32 Lamp driver annunciator control module; For use with custom graphic annunciators; 32 points
LDM-R32 Relay module; 32 form-A contacts; Connects yo Ldm-32 or Ldm-E32
SCS-8 Smoke control master; Includes 8 on/off/auto switches
SCS-8L Smoke control lamp driver; Outputs for 8 on/off/auto Sw/LED’S; For custom built smoke control
stations
Panel Circuits
UDACT Universal digital alarm communicator transmitter
DPI-232 Direct panel interface; Modem interface for direct wire (no dial-up capabilities) for interconnecting
panels; Replaces Tpi-232 in direct wire applications
LCM-320 Loop control module, clip/flashscan
LEM-320 Loop expander module; Mounts as daughter board to Lcm-320 to provide even numbered
Slc loops
Networking & Interfaces
NCM-x Network control module – copper or fiber optic models available
RPT-485W Twisted pair Eia-485 repeater; Increase Eia-485 capacity by 32 devices; Mounts to Chs chassis
position or Abs-8R box
RPT-F Network fiber optics repeater
BACNETGATEWAY Interface between Xls-Net and BACnet protocol
XLS-NCM-EBI-F Ncm-F for Honeywell EBI only
XLS-PRN-6 80 column desktop printer, 120 Vac
Q7055B1039 Fire network adapter, interface for EBI
XLS140 Equipment
KDM-2 Keyboard display module; 80-character display and keypad
XLS140-CPU XLS140 Central Processing Unit – 120 Vac; Includes built-in power supply
XLS-FDU-80 80 character display annunciator – horizontal design
XLS-LCD-80 80 character LCD annunciator – vertical design
XLS3000 Equipment
AMPS-24 Primary power supply for Xls3000, 120 Vac
CHS-M3 Mounting chassis for XLS3000 CPU
LCD-160 Remote annunciator for Xls3000, 160 characters
XLS3000-CPUD XLS3000 CPU with display
XLS-ELCM-320 Loop control module, Eclipse (Honeywell)
XLS-ELEM-320 Loop expander module, Eclipse (Honeywell)
XLS-NCA2 Network control annunciator, Honeywell
XLS-DVC Equipment
CMIC-1 Chassis with paging microphone
DAA-xxxx Digital amplifier, 120 Vac, 50 W, 25-70.7Vrms, copper or fiber optic communication
DVC-AO Digital voice command, analog output
DVC-KD Digital voice command, keypad
MIC-1 Paging microphone only
TELH-1 Firefighter’s telephone handset only
XLS-DVC-EMx Digital voice command (Dvc), expanded memory, copper or fiber optic communication
A Flexible, Highly Integrated CCTV Solution
with Advanced Capabilities
PRODUCT FEATURES:
• Software-based digital CCTV video management platform
Uses off-the-shelf PC, storage and networking hardware
• Live viewing and playback while recording
Camera pan/tilt/zoom control from any client on the network
Continuous, scheduled, alarm, pre-alarm motion and user-activated recording modes
Up to 30fps performance on all channels
Communicates using TCP/IP network protocol using industry-standard Ethernet technologies
Full integration with EBI including direct access to alarm recordings from EBI alarm/event
summary display
• High-speed SQL-based search engine (date, time, camera, operator, point, alarm)
Digitally signed recordings and audit trail
Advanced fault-tolerant solutions with optional Redundant Database Servers and Redundant
Camera Servers
Optional Distributed Video Architecture – analogous to EBI’s DSA – allows the connection of
multiple systems into a single, homogenous surveillance solution
• Advanced video analytics capability
• Camera tamper detection features camera blinding, blurring and changed field of view detection
DVM Database Server
Manages the DVM system; Contains recording index, audit log and Web server
• (1) database server per system
• (1) optional redundant database server per system
Uses off-the-shelf PC with the following minimum specifications:
Recommended Processor: ......Intel Xeon 5130 or greater (or AMD equivalent), depending on
system requirements
System Memory (RAM): ..........1GB RAM minimum; 2GB recommended
Hard Drives: ...........................Two separate hard drives (or sets of RAID drives)
Disk 1: 40GB Windows Operating System, DVM database server
software, Microsoft SQL Server Software
Disk 2: 80GB DVM database files, Microsoft SQL Server database files
Load Device: ..........................DVD drive
Network Connection: ..............DELL onboard NIC or compatible NIC
Must be 100MB or greater
Video Resolution: ....................1024x768 pixels; 65k colors non-interlaced
DVM Camera Server/Analytics Server
Stores video streams and transmits video to clients; Number of database servers required
dependent on application, minimum of 1 per system
Uses off-the-shelf PC with the following minimum specifications:
Recommended Processor: ......Intel Xeon 5130 or greater (or AMD equivalent), depending on system
requirements. Additional CPUs recommended for servers managing
Video Motion Detection and advanced video analytics (2 processors or
dual core) 3.2GHz or greater recommended for VMD
System Memory (RAM): ..........1GB minimum plus pre-record requirements
Hard Drives: ...........................40GB for operating system; Second disk or disk array for video recording
storage
Load Device: ..........................DVD drive
Network Connection: ..............DELL onboard NIC or compatible NIC
1GB NIC minimum recommended
Video Resolution: ....................1024x768 pixels; 65k colors non-interlaced
Optional Video Storage Subsystem (Rorke Data or Bell Micro)
Provides additional fault tolerant (RAID-5) video storage. Scales from 10’s to 100’s
of terabytes. DVM supports any Windows 2000-compatible off-the-shelf storage device
including Direct or Network Attached Storage (DAS or NAS) or Storage Area Network
(SAN) systems
Off-the-shelf storage subsystem with the following minimum specifications:
RAID Levels: ...........................0, 1, 3, 4, 5 and 6
Redundancy: ..........................Hot-swappable drives, hot-sparing, redundant power supplies, redundant
RAID controller
Drives Supported: ...................4, 8, 14, or 42
Drive Types: ...........................Ultra ATA/133, Ultra ATA/100, or SATA
Data Rebuild:..........................40GB storage
RAID Controller: ......................RAID-5 fault tolerant storage, capacity dependent on application
SCSI Interface: .......................SCSI Ultra160
O/S Supported: .......................Windows 2000/2003
Honeywell UltraKey Keyboard – Programmable Keyboard Controller
UltraKey Lite, UltraKey Plus and legacy UltraKey (HEGSA002)
Secure operator sign-in to the system
Select "command + cameras/views" to view surveillance monitors
Control PTZ cameras and start/stop recordings
Commands accessed and issued dynamically by hard-key or soft-key selection via Ultrakey's
programmable LCD
Network Switches
DVM Communicates using TCP/IP network protocol using industry-standard Ethernet
technologies. The network switch links the video streamers to the camera server(s) and
camera servers to clients.
Off-the-shelf storage network switches with the following minimum specifications:
Simple Network Management Protocol (SNMP)
IEEE 802.1D bridging capability and loop detection
IEEE 802.1Q tagged VLANs
IEEE 802.1 traffic prioritization for multiple QoS levels
Support for multicast traffic
Non-blocking, wire-speed access across all ports
IP Network Cameras
IP Network cameras combine the video encoding and streaming functions of the video streamer with
a security camera; Digital video streams are transmitted across a standard LAN/WAN to DVM Camera
Servers for indexing and storage
Honeywell: .............................High Resolution “Box” Camera and Mini-Dome
EQUIP: HCD554IP(X), HCS554IP(X), HD4DIP(X), HD3MDIP(X), HD4MDIP(X)
Honeywell Megapixel Cameras: HCX13M, HCX3, HCX5D supporting resolutions from 1.3MP to 5MP
Axis: .......................................M-Series: M1011, M1011W, M1031W, M1054, M1103, M1104, M1113,
M1114, M3011, M3014, M3113-R, M3114-R, M3203, M3204
P-Series: P1311, P1343, P1344, P1346, P1347, P3301, P3304, P3343, P3344
Q-Series: Q1755, Q1910
Previous Series: 205, 206, 206W, 207, 207W, 207MW, 209FD, 209MFD,
210, 210A, 211, 211A, 211M, 216FD, 216MFD, 221, 223M, 225FD
Sony: ......................................IPELA: Multiple generations
..............................................Gen2: SNC-DF40; Gen3: SNC-CS50, SNC-DF50; Gen4: SNC-DS10, SNC-
DS60, SNC-CS20
Panasonic:..............................i-Pro Series: WV-NP244, WV-NP502, WV-NW-484
Bosch: ....................................Dinion NWC-0455, FlexiDome NWD-455
High Speed PTZ Domes & PTZ Cameras
18X, 23x, 25x and 35x zoom with indoor and outdoor housings
Honeywell: .............................ACUIX 18X, 23x, 25x and 35x zoom with indoor and outdoor housings;
EQUIP: HDXxxxDxxx (see DVM Compatibility Matrix for more information)
Axis: .......................................P-Series: P5532, P5534, P5544
Q-Series: Q6032, Q6034
Previous Series: 212 (Digital PTZ), 213, 214, 215, 231D/231D+,
232D/232D+, 233D
Sony: ......................................IPELA: Multiple generations
Gen2: SNC-P5, SNC-RZ25; Gen3: SNC-RX530, SNC-RX550, SNC-RX570,
SNC-RZ50
Panasonic:..............................i-Pro series: WV-NS202, WV, NS954, WV-NW964
Bosch: ....................................AutoDome 300 Series
Honeywell RapidEye – Streamer and Digital Video Recorder
RapidEye Multi Media DSP
RapidEye Multi Media
RapidEye Multi Media LITE
Single/Multi Channel Encoder/Streamer
Honeywell: .............................Legacy devices: HNVE130A
Axis: .......................................M-Series: M7001
Q-Series: Q7401, Q7404, Q7406
Previous Series: 240Q, 240Q Blade, 241S, 241S Blade, 241SA, 241Q, 241Q
Blade, 241QA, 243SA, 243Q Blade, 247S
Analog Cameras
Full range of cameras/lenses from entry level models through to Ultra Wide Dynamic models
Fixed Camera
Honeywell: .............................L-Series, Ultra Wide Dynamic, Miniature High Resolution, indoor mini-
domes and indoor/outdoor vandal domes
Other: .....................................Any NTSC or PAL analog camera
Pan/Tilt/Zoom (PTZ) Camera
Honeywell: .............................Honeywell Video Systems, Ultrak UltraDome, ACUIX 18X, 23x, 25x and
35x zoom with indoor and outdoor housings, RapidDome/VCL, Orbiter,
HD6 Series
Other: .....................................American Dynamics Speed Dome, Bosch AutoDome G3A, Canon VC-C3/
C4/C4R, Daiwa DMP 15, Ernitec Orion, Lilin FastDome, Molynx Surcha,
Panasonic WVCS850/854, Pelco SpectraDome, Sony EVI-D30/D31/G20/G21
Honeywell Digital Video Manager
Ethernet
Analog Cameras
Analog Cameras
System Description
Base System Includes 50 meters
Meter Pack Option 1 10 meter
Meter Pack Option 2 50 meter
Meter Pack Option 3 100 meter
Meter Pack Option 4 250 meter
Meter Pack Option 5 1000 meter
Options
Advanced Energy Modeling Add-on to base
Enterprise Load Management Add-on to base
Web Reporting Add-on to base
Weather Data Add-on to base
Architecture Requirements
Energy Manager must be installed on its own dedicated server and interfaced to your existing facility
management network via open system integration
Ethernet
Energy Manager – Understand and Control Energy
PRODUCT FEATURES:
“Out-of-the-box” solution for energy data collection, validation, analysis and reporting
Flexible, hierarchical modeling of your facility, plant and meters
Automatic data cleaning removes or reduces the impact of meter failures, dropouts and spikes
Exceptionally powerful reporting and analysis. Compatible with most utility meters and sub-meters; Supports
electric, gas, water, fuel oil and other meter types
Automatic load shedding and generator control based on demand limits and configurable algorithms
• Energy load forecasting
Weather data can be read from local weather stations or the internet for use in reporting and analysis
Greenhouse gas emission tracking
Honeywell Energy Manager
Utilities/Meters
Supported
Electrical
Gas
Water
Propane
Liquid Fuel
• Fuel Oil/Heavy Fuel
Steam and Super Heated
Steam
Chilled & Heated Water
Solid Fuels
Compressed Air
Argon
Nitrogen
Coal
Wood
Sewage
Meter Management
Modbus
Pulse Accumulators/Totalizers
LonWorks
OPC
EXCEL 5000
BACnet
Data Validation and Estimation
Thermal Calculations
Virtual Meters
Text-file Import
Equipment Run-hours
Meters
Veris Industries (www.veris.com)
Power Measurement Limited
(www.pwrm.com)
• Square D (www.squared.com)
• WattNode by Continental Controls
(www.ccontrolsys.com)
TCP/IP
LON
LonWorks
Meter
Pulse
Pulse
LonWorks
Wireless Meter
E-Mon
i.LON
®
600 Router
Provides network connectivity between
Ethernet LAN and LONTalk (FTT-10A) bus
Wireless Meters
• Honeywell (E-Mon)
-Class 100
-Class 200
-Class 500
ModHopper
ELPRO
• IO Select
Benefits of Energy Manager
Identify and reduce peak energy demands that are driving up costs
Implement powerful load curtailment strategies
Validate and understand utility data
Optimize equipment start and stop times
Negotiate lower energy rates
Uncover employee equipment overrides that increase costs
Energy Manager Foundation
Energy Manager Foundation is built upon modeling your Energy System; This model describes the objects within your
facility, and the relationships between them; Objects that can be integrated into your Energy System Model include:
Meters (real and virtual)
Localities (geographical locations, campus, building, floor and central plant building area)
Equipment (AHU, lighting, boiler, chiller, generator, etc.)
• Circuits (grouping of loads and generators)
Tenants
Weather stations
Cost Allocation
Rate design and utility tariff modeling
Tenant billing and utility bill validation
Supports time-of-use, seasonal charges, peak demand, taxes and tiered charges
Invoice management and reporting
Web Reporting
Intuitive pre-built reports accessible from your Web browser
• Scheduled e-mail delivery of reports
Facility Demand Management
Load monitoring with automatic alarming and event logging
Automatic load shedding and generator control can be managed according to various algorithms to curtail costly
spikes in demand peaks
Load management operator displays provide real-time visualization and tuning
Energy Load Forecasting
Batch oriented forecasting tool that predicts energy demand based on historical usage
Uses local-regression technology to forecast future energy demand
• Forecasts hourly consumption 45 days in advance
Forecasts regularly re-computed as the horizon decreases
Rates Engine
Configures tariffs in the system
Calculates individual charges and total costs
• Different rates can be applied depending on level of consumption or time of use
Rate Builder
Engineering configuration tool for modeling rates (tariffs)
Internationalization
Energy Manager is available in local languages
Server and Client Requirements
Per current EBI Release
Licensing
• Energy Manager Foundation license model is based upon the total number of meters; An initial 50
meters are included with this license
• Additional meters can be added in 10-pack increments
Advanced Energy Modeling, Enterprise Load Management and Web Reporting are sold as add-on
options to Energy Manager Foundation
EXCEL 5000 OPEN
, Excel Building Supervisor
(XBS), Excel Building Supervisor Integrated
(XBSi), Excel Plus
, Excel Classic
, Excel 800
, Excel 500
, Smart Excel
500
, Excel 50
, Excel 10
, Excel Security Manager
, Excel Life Safety
(XLS/XLS140/XLS1000/XLS3000), Eclipse
, Delta 1000
, Delta 2000
, Honeywell Instant Alert
®
,
Intelliguard 9000
(i9000), PipeIQ
, Reveal
,Temaline
®
, Galaxy
, Vista
and DeltaNet FS90
are trademarks or registered trademarks of Honeywell International Inc.
AWACS
is a trademark of Boeing, Inc. FlashScan
®
is a registered trademark of Library Automation Technologies, Inc. Modbus
®
is a registered trademark of the
Modbus Organization, Inc. Niagara
AX
is a trademark of Tridium, Inc. Sylk
is a trademark of Microsoft, Inc. L-IP
®
is a registered trademark of Loytec electronics GmbH.
All other brands are trademarks of their respective companies. Above information subject to change without notice.
77-2148
May 2011
© 2011 Honeywell International Inc.
Printed in the USA on recycled paper
containing 10% post-consumer waste.
PRODUCT FEATURES:
Smarter Security
Secure DESFire smart card credential
• Digital certificate versus just a card number
• Encrypted transaction – card to reader –
Reader to EBI
User-managed encryption keys
Vulnerable central controller eliminated
Scalability
Unlimited cardholders per door
• Up to 20,000 doors can be assigned per
cardholder
• Up to 20,000 doors per system – add one
door at a time
LAN/WAN connectivity across the Enterprise
Flexibility
• IP – PoE, Wi-Fi or standalone configurations
Multi-use/application smart card credentials
• Compatible with existing Honeywell access
systems (PCSC/NexWatch/Temaline)
Simpler
Simple threat management for faster critical
event response
Flat architecture
IT-managed connectivity all the way to reader
Simpler commissioning and management
from EBI
IdentIPoint
System – Intelligent Fingerprint Reader
P/N – BTFPT
• ARM 9 CPU
• Real-time clock and calendar
• MIFARE Classic & DESfire support
Wireless and wired Ethernet
• PoE or 12 to 24 VDC
Dual tamper protection
1 output, 3 inputs – supervised
1 Relay output
Digital certificate on card
Embedded controller
Embedded Linux
• LED & LCD display
• Keypad for PIN
10,000 transaction buffer
• CE / FCC
• Connection to IO Module
• Antipassback on smart card – global and nested
Encrypted – 128 AES communication with host
• DHCP Client support
IdentIPoint
System – Intelligent Standard Reader
P/N – BTSTD
Identical specifications to BTFPT but excludes fingerprint reader
IdentIPoint
System – Intelligent Basic Reader
P/N – BTBAS
• Identical specifications to BTSTD but excludes LCD and keypad
Outdoor use – IP 65 rated
RS-485
IdentIPoint
System – Input Output Module (IOM)
P/N – BTIO
For use on secure side of door
Makes it possible to control one door using two readers in IN &
OUT mode
Max 4 IOMs with one reader
Encrypted RS-485 communications with reader – 3-DES
Relay: 2 – (1A 24VDC) Form C
Digital Inputs: 2
Digital Outputs: 2 (current sinking; max 24V 1A)
Supervised Analog Inputs: 4 – capable of distinguishing 4 states
Supervised Analog Outputs: 1 – repeats the last supervisory input,
SAI3
• 12 to 24 VDC operation
Tamper protection
• CE / FCC
IdentIPoint
System – “Standalone Reader”
Any of the readers above can also be used in “standalone mode”
• Set up as standalone during commissioning
Transactions transferred using card as a carrier
• Use where physical wiring is difficult and/or no network connection
is available
• Use where online events and alarms are not needed
Operates with or without an IOM
Ethernet
XLS-NET
Twisted Copper Pair
CP-IPC Network Controller
Specification Data Sheet SL-53-1092 AP
• BACnet, BTL listed Building Controller (B-BC
profile)
Freely Programmable and Standard Applications
• Includes 24 I/O expandable to 128 I/O using
CP-EXPIO (4-DO, 6-DI, 6-AO, 8-UI)
Ethernet IP connection for BACnet over IP
communication
• Includes 3 MS/TP ports to support up to 90
devices
ComfortPoint Studio programming tool
Integral BACnet Router capability
CP-DIO
Specification Data Sheet SL-53-1092 AP
CP-IPC Digital Input/Output Expansion board
and controller
• BACnet, BTL Listed Advanced Application
Controller (B-AAC profile)
32 Standard Input/Output points for control and
monitoring, or custom program
Onboard Input/Output (8-UI, 8-DI, 16-DO
• ComfortPoint Studio for configuration and
programming
CP-EXPIO:
CP-IPC Expansion Board
Specification Data Sheet SL-53-1092 AP
24 Input/Outputs (4-DO, 6-DI, 6-AO, 8-UI)
• Up to 15 CP-EXPIO expansion boards per CP-IPC
ComfortPoint Studio for configuration
CP-VAV:
Specification Data Sheet SL-53-1092 AP
• Unitary, Variable Air Volume (VAV) freely
programmable controller
• BACnet, BTL Listed Application Specific
Controller (B-ASC profile)
Built-in Real Time Clock
20 integral Input/Output points (8 DO, 4 DI, 2 AO,
6 AI) and air flow sensor
ComfortPoint Studio tool for configuration and
programming
CP-SPC:
Specification Data Sheet SL-53-1092 AP
Small Point Controller (SPC) is freely
programmable
• BACnet, BTL Listed Application Specific
Controller (B-ASC profile)
Built-in Real Time Clock
• Standard FCU applications, or flexible custom
programming
Onboard I/O (8 DO, 4 DI, 2 AO, 5 AI)
ComfortPoint Studio tool for configuration and
programming
BACnet MS/TP
CP-IPC
Network Controller
BACnet Router
CP-5050
BACnet Router
Specification Data Sheet SL-85-3018
Supports BACnet/IP, BACnet Ethernet and 4
RS-485 ports for MS/TP Networks
BACnet connectivity option
Reveal
TM
Specification Data 74-5088
Touchscreen LCD
• Grayscale and full color backlit
display
Customizable user screens
Permission-based access
Access to system data and alarms
Access all controllers on the
Niagara network
• Configured via the ComfortPoint
Programming Tool (CPT)
CP-UL1012S, CP-UL4024S
Unitary application
No Velocity Pressure Sensor
No Floating Actuator
CP-UL1012 S
-1 Universal Input (UI)
-0 Digital Inputs (DI)
-1 Analog Output (AO)
-2 Digital Output (DO)
CP-UL4024S
-4-UI, 0-DI, 2-AO, 4-DO
CP-VL0000AS, CP-VL4022AS
VAV Application includes:
-Velocity Pressure Sensor
(Microbridge)
-Series 60 Floating Actuator
CP-VL0000AS
-0-UI, 0-DI, 0-AO, 0-DO
CP-VL4022AS
-4-UI, 0-DI, 2-AO, 2-DO
CP-VL4024NS
Velocity Pressure Sensor (Microbridge)
No Floating Actuator
CP-VL4024NS
-4-UI, 0-DI, 2-AO, 4-DO
ComfortPoint LonMark Certified
Application Specific Controllers (ASC)
Specification Data Sheet SL-74-5153
Configurable via LNS Plug-in
Applications (LonMark Functional Profiles) supported:
-VAV-ATU w/actuator (CP-6436AS-VAV-LM)
-VAV-ATU no actuator (CP-6438NS-VAV-LM)
-RTU (CP-6438-RTU-LM)
-WSHP (CP-6438-WSHP-LM)
-FCU (CP-6438-FCU-LM)
-UV (CP-6438S-UV-LM)
-Modified Application (CP-6438-SPL-LM)
LON connectivity option
LON Bus option to Excel 5000 Open Controllers
in lieu of BNA, or OVN C-bus connectivity
i.LON
®
600 Router
Provides network connectivity between
Ethernet LAN and LONTalk (FTT-10A) bus
UUKL version available where smoke
control required
Loytec L-IP Router
Routes packets between CEA-
709 and IP (Ethernet) Networks
• “Smart Switch” & “Configured
Router” Modes Supported
Open View Net (OVN)
Q7055B1047; Specification Data
74-4021
Web enabled operator interface
Excel 5000 point auto-
discovery
• Alarming & data and
diagnostics
PDA remote access
IdentIPoint
Access Control
System
An IT-Friendly Smart Card Access Control Platform
Logitech
®
Webcam Pro 9000
P/N 960-000577
Photo ID Workstation
Quad Core Intel
®
Xeon
®
Processor
Integrated Gigabit Ethernet
• Hard drive size configurable to meet customer
requirements
Canon Powershot A495
• P/N 4259B001
inPhoto ID PS Canon Interface
P/N IPIPS
Seitenansicht 0
1

Inhaltsverzeichnis

Seite 1 - Local Area Network (LAN)

PRODUCT FEATURES• A family of distributed control products that are open and easy to use, the EXCEL 5000 OPEN System is a proven performer that defin

Kommentare zu diesen Handbüchern

Keine Kommentare